底部版权

Splend Electric (Beijing) Co., Ltd
Tel:+86 10 50842888
Fax:+86 10 50842886
E-mail: splend@splendpower.com
Http:www.splendpower.com
Add:52A, No.17 Jing Sheng South 4th Street, Zhongguancun Science and
Tec hnology Park, Tongzhou District, Beijing-China
Mobile phone
website
WeChat two-dimensional code
Copyright: Splend Electric (Beijing) Co., Ltd. 京ICP备10023425号
product center
Active Voltage Conditioner
Active Voltage Conditioner
The SDUC® is an inverter-based system that protects sensitive industrial and commercial loads from voltage disturbances. Providing fast, accurate voltage sag and surge correction as well as continuous voltage regulation and load voltage compensation. The SDUC® has been optimally designed to provide equipment immunity from power quality events on the supply network.
How it works
The SDUC® consists of two converters that are not on the current path between the load and the utility. Instead, the corrective voltage injection is achieved by means of a transformer winding between the utility and the sensitive load.
This configuration results in a very efficient and effective method to provide voltage correction with reduced risk of negative impacts on the load.
Design
Frequency |
50Hz ±5% o 60Hz ±5% |
Voltage regulation |
IGBT controlled (double conversion technology) |
Adjusting energy parameters |
Independent phase control |
Selectable target voltage |
380-400-415V (440-460-480V**) |
Output voltage accuracy |
±0,5% |
Admitted load variation |
Up to 100% |
Admitted load imbalance [%] |
100 |
Cooling |
Forced ventilation |
Ambient temperature |
0/+40°C |
Storage temperature |
0/+60°C |
Max related humidity |
<95% (non condensing) |
Admitted overload |
150% for 1 minute (at nominal input voltage) |
Colour |
RAL 7035/7032/9005 |
Instrumentation |
10" touch panel, multilingual (on request remotely available by dedicated software connected to the same Ethernet network) |
Installation |
Indoor |
Communication system |
MODBUS TCP/IP |
Overvoltage protection |
Class I input surge arrestors Class II output surge arrestors |
Additional protections |
Automatic by-pass protection |
Technical parameter
Inquire about the company or Email:splend@splendpower.com