Static Var Generator
Static Var Generator
Introduction
The principle of the SVG is very similar to that of Active Power Filter, as demonstrated in the picture below. When the load is generating inductive or capacitive current, it makes load current lagging or leading the voltage. SVG detects the phase angle difference and generates leading or lagging current into the grid, making the phase angle of current almost the same as that of voltage on the transformer side, which means fundamental power factor is unit.
Splend Electric series SVG is also capable of correcting load imbalance.
SVG Principle
SVG Structure
Splend Electric Series SVG is also modular in design, and the SVG system consists of one or several SVG modules and an optional Liquid Crystal Monitor & Control Panel (SD-8). Each SVG module is an independent reactive power compensation system, and users can change the SVG rating by adding or removing SVG modules.
SVG modules and LCM panel can be embedded in Splend’s standard SVG cabinet or in a customized cabinet. There are usually breakers, cable terminals and Surge Protection Device (SPD) in the SVG cabinet.
FEATURES
Multifunctional |
Reactive power and imbalance compensation |
Excellent reactive compensation |
High speed, Precise (-0.99≤Cosφ≤0.99), Step-less, Bi-directional (capacitive and inductance) compensation |
Excellent imbalance correction |
Both negative and zero sequence, mitigates neutral current |
|
Wide input voltage & frequency range, adapts to tough electrical environment |
loss&efficiency |
Low thermal loss (≤3% of rated SVG capacity), efficiency ≥ 97% |
High stability |
Infinite impedance to grid, avoids harmonic resonance problem |
Flexible application |
Modular design, embedded in standard or customized cabinet |
Easy installation and maintenance |
Easy installation for SVG module replacement and expansion |
Wide capacity range |
50kvar~400kvar for a single cabinet, up to 10 cabinets in parallel |
Environmental adaptability |
-10~50°C temperature, compatible with diesel generators |
Complete protection |
Grid over/under voltage, SVG over current, over temperature, and others. All faults recorded inevent log, convenient for failure analysis |
Technical parameter
Product Type |
SDG-**-M-0.4kV |
SDG-**-M-0.69kV |
Rated voltage |
380VAC±10% |
690VAC±10% |
Rated frequency |
50(60)Hz±3%,With automatic frequency sweeping function |
|
Plant type / number of phases |
3 phases, 3 wires or 3 phases, 4 wires |
|
Main network distribution |
TN or TT |
|
Cosφ pfc |
0.99 from capacitive to inductive |
|
Harmonic compensation |
up to 13th , individually selectable |
|
Compensation method |
Compensate reactive power (full capacitive~inductive), filter specific harmonics (less than 13th ), and solve three-phase imbalance |
|
Response time |
≤5ms |
|
Graphic interface |
7” display touch screen unit for commissioning and monitoring. Includes Ethernet interface |
|
Operation mode |
Automatic or Manual |
|
SVG module capacity Modular system |
400V:25Kvar、35Kvar、50Kvar、75Kvar、100Kvar、125Kvar 690V:50Kvar、60Kvar、100Kvar、120Kvar |
|
Multiple modules can be used in parallel |
||
SVG Cabinet capacity |
400V:100Kvar、200Kvar、300Kvar、400Kvar、500Kvar 690V:100Kvar、200Kvar、300Kvar、400Kvar、500Kvar |
|
Protection degree |
IP32 (for floor mount cabinet) IP20 (for wall mount version) IP54 (optional for floor mount) |
|
Colour |
Optional |
|
Cooling |
forced ventilation |
|
Ambient temperature |
from -15°C to +45°C full performance, derating up to 55°C |
|
Relative humidity |
<95%, non condensing |
|
Altitude |
2000m, 4000m max with derating |
|
Certificates |
CE, ROHS |
Technical parameter