Products

Products


+
  • 接触器投切-.jpg

SD-MV Series Filter Module

Use occasion Fully automatic reactive power compensation, can be installed directly. It is used for centralized compensation of reactive power in three-phase power grid with serious harmonic pollution. Upper limit of harmonic pollution in use: U3 max.0.5%, U5 max.5%,U7 max.4%.

Product Description

SD-MV series reactive power compensation module

 

Use occasion

  • Fully automatic reactive power compensation, can be installed directly.
  • It is used for centralized compensation of reactive power in three-phase power grid with serious harmonic pollution.
  • Upper limit of harmonic pollution in use: U3 max.0.5%, U5 max.5%,U7 max.4%.

 

Standard

Technical standards: EN60439-1, EN60831-1, IEC439-1

 

Operating conditions

Rated voltage: 230V-690V

Rated frequency: 50Hz/60Hz

Withstand voltage test: according to the standard

Cooling method: forced air cooling

Ambient temperature:-15 to 50°C (65°C high)

Altitude:<2000m a.s.l.(≤ 5000m optional)

Relative humidity: 10…95% (no condensation allowed)

Installation conditions: indoor installation. For outdoor installation, please contact us

 

Design

SD-MV®Reactive power compensation and harmonic control integrated drawer module
Fully automatic control, contactor switching

Capacitor UN = 480V, Overcurrent Capability: 1.5In

Single cabinet kit, IP00, without cabinet body.

Warranty period: 30 months
Reactivity rate: 5.67%,7%,8%,14%
Rated voltage: 230~690V (max. + 10% within 8 hours per day),50/60Hz
Protection grade: IP20 or IP00; For IP54, please contact us.
Temperature rating: -20/B (24 hours average temperature 35 ℃). For higher, welcome to inquire.

Modular components

  • High-load, gas-filled, low-loss, self-healing capacitors with over-pressure protection.
  • Vertical busbar system with low voltage fuse protection
  • Special contactor
  • Filter reactor, with temperature monitoring, low loss, full vacuum impregnation.
  • Temperature monitoring

Next Page